Page 38 - ATREA3 EN_2

Basic HTML Version

ACOUSTICS, BASIC UNIT
S O U N D P O W E R L E V E L L ( A ) ( d B )
W
External pressure p (Pa)
st
0
200
0
2 000
3
Volume flow rate (m /h)
1 000
800
600
400
500
1 000 1 500
1
4
7
2
5
8
3 6 9
For detailed calculation we recommend a special selection
software be used.
1
84,1
60,7
66,5
2
75,0
50,5
57,9
3
56,5
34,9
42,8
4
82,0
59,8
66,8
5
73,9
51,0
57,7
6
54,8
36,1
42,8
7
82,5
60,6
68,5
8
73,7
50,6
58,3
9
55,3
35,6
44,5
point
outlet (dB(A))
inlet (dB(A))
surround. (dB(A))
DUPLEX-S 1600
External pressure p (Pa)
st
0
200
0
3 000
3
Volume flow rate (m /h)
1 000
800
600
400
500 1 000 1 500
1
4
7
2
5
8
3 6 9
For detailed calculation we recommend a special selection
software be used.
1
78,7
56,9
72,3
2
64,0
45,0
58,9
3
45,9
30,2
43,4
4
79,6
55,2
72,7
5
63,7
43,6
58,0
6
44,9
29,9
43,7
7
80,5
55,7
74,7
8
65,1
43,0
59,0
9
45,6
30,1
43,7
point
outlet (dB(A))
inlet (dB(A))
surround. (dB(A))
2 000 2 500
DUPLEX-S 2600
Hous i ng
The housing unit is manufactured of panels with painted sheet metal and a polyurethane insulation of 30 mm thickness
-2 -1
(U = 0,82 Wm K ), T3 class, TB3. Front door enables easy access to all built-in components.
D U P L E X - S – B A S I C U N I T
Me.xxx; Mi.xxx
DUPLEX-S xxxx
Fans
For both the supply and exhaust air, high-performance EC fans are used (direct drive wheel in semispiral housing with
fitted spring-mounted electric motor). Due to the fans; the units are highly efficient with very low specific power input.
Hea t r eco v e r y co r e
The units are equipped with a newly designed high-performance heat recovery core. This is made of thin plastic plates
with high recovery efficiency up to 93 %.
By - pass dampe r ( „B“ )
The heat recovery core bypass, includes an actuator. When opening the by-pass damper, airflow through the
recovery core closes automatically to avoid heat transfer.
B.x
S4.A.H / S5.A.H
External pressure p (Pa)
st
0
200
0
3
Volume flow rate (m /h)
1 000
800
600
400
1000 2 000 3 000
1
4
7
2
5
8
3 6 9
For detailed calculation we recommend a special selection
software be used.
1
87,6
67,7
71,6
2
71,9
56,1
57,3
3
52,8
37,4
42,3
4
85,9
66,6
69,3
5
70,2
54,7
56,1
6
53,0
36,5
42,4
7
87,5
64,2
68,7
8
70,8
52,8
56,0
9
53,1
35,5
42,1
point
outlet (dB(A))
inlet (dB(A))
surround. (dB(A))
4 000
DUPLEX-S 3600