FLOOR-STANDING POSITION
CEILING-SUSPENDED POSITION
view with
installation
opening
min. B + 30
floor
min. L / 2 + 100
FORNT VIEW
TOP VIEW
L / 2 + 100
door
Manipulation space, unit configuration
min.
600
min.
600
140
23
23
L / 2
L + 50
L / 2
23
73
H - 50
25
Z1
Z2
35
Z3 25
L/2 - 275
L/2 + 25
50
50
K
K
K
MANIPULATION SPACE, ACOUSTICS
When installing DUPLEX-S units it is necessary to allow
Minimum manipulation space required for the hinged door is
marked on respective drawings.
for the recommended free space around the unit to allow for
manipulation. A minimum space of 150 mm is needed under
For all units 600 mm free manipulation space from an electric
the unit to install a DN 32 condensate drain pipe. A trap with
control panel, is required in accordance with respective
standards.
a minimum height of 150 mm must be installed before connecting
the pipe to a building sewer. The recommended space is easily
ensured when the standard support steel legs are used.
Space in front of the unit is required for opening the door, filter
changing and access to all components that require service.
M A N I P U L A T I O N S P A C E
Unit
Support legs
Suspension point - Chiller
Suspension point - Unit
Suspension point - Chiller
DUPLEX-S 1600
5 pcs
1 pc
4 pcs (in corners)
2 pcs
DUPLEX-S 2600
6 pcs
1 pc
4 pcs (in corners)
2 pcs
DUPLEX-S 3600
6 pcs
1 pc
6 pcs (in corners and in the middle)
2 pcs
Unit
L
Z1
Z2
Z3
B
H
DUPLEX-S 1600
2 020
418
750
392
490
1 270
DUPLEX-S 2600
2 150
566
875
540
570
1 570
DUPLEX-S 3600
2 450
625
875
600
780
1 660
 11