M A N I P U L A T I O N S P A C E
Floor-standing horizontal
DUPLEX-S 1500 to 5600
Ceiling- suspended
DUPLEX-S 1500 to 4500
Floor-standing vertical
DUPLEX-S 1500 to 5600
Floor-standing flat
DUPLEX-S 1500 to 4500
min. T
min. 80
min. 150
min. U
min. U
min. - see actual
unit size
K
MANIPULATION SPACE
When installing DUPLEX-S units it is necessary to allow
Each individual drawing shows the minimum manipulation distance
when hinged door is used (easier access), and minimum
for recommended free manipulation space around the unit.
manipulation space for hingeless door, with quick locks (more
Minimum space of 150 mm is needed under a unit to install
difficult access).
a DN 32 condensate drain pipe. A trap of minimum height
For all units a minimum 600 mm of manipulation space must be
of 150 mm must be installed before connecting the pipe
left on side where an electrical control panel is located according.
to a building sewer. The recommended space is easily ensured
For units equipped with a heating or cooling hydralic kit a free
when delivered standard support steel legs are used.
space on side of the kit must be left.
Unit front service space is needed for opening access door, filter
removal and access to all components for maintenance.
140
without coil
2 coils hingeless
T =
1 coil
DUPLEX-S 1500 1 150
1 150 440
DUPLEX-S 2200 1 260 1 260 570
DUPLEX-S 3100 1 260 1 325 650
DUPLEX-S 4500 1 260 1 325 870
DUPLEX-S 5600 1 260 1 325 1 050
without coil /1 and 2 coils
U =
hinged
hingeless
DUPLEX-S 1500 1 300
440
DUPLEX-S 2200 1 350
570
DUPLEX-S 3100 1 520
650
DUPLEX-S 4500 1 520
870
DUPLEX-S 5600 1 520
1 050
Hydraulic kits
Control modules
K
Hinges
Hinges
K
Hinges
View with an
installation opening
(also to access
the electric RMD
and a hydraulic kit)
K
min. 150
min. 150
K
min. 600
RMD, RMT, RMCH
SR, SR-T
min. U
200
K
min.
600
R-TPO / R-TPO-3 / RS-TPO
R-CHW / RCHF
ÚT
Hinges
Hinges
S O U N D P O W E R L E V E L L
W
S O U N D P R E S S U R E L E V E L L
D 1
Type
Fan
Oper. point Sound power L [dB(A)]
w
inlet e ,i
56,6
1 1
230 V
M.005
outlet e ,i
72,5
3
2 2
1 000 m /h
DUPLEX
unit
62,2
S-1500
inlet e ,i
57,0
1 1
230 V
M.007
outlet e ,i
74,5
3
2 2
1 300 m /h unit
63,4
inlet e ,i
60,6
1 1
DUPLEX
230 V
M.014
outlet e ,i
75,6
3
2 2
S-2200
1 800 m /h unit
61,8
inlet e ,i
62,8
1 1
400 V
M.010
outlet e ,i
81,7
3
2 2
2 650 m /h
DUPLEX
unit
67,9
S-3100
inlet e ,i
53,4
1 1
230 V
M.014
outlet e ,i
76,1
3
2 2
2 100 m /h unit
61,4
inlet e ,i
62,7
1 1
400 V
M.011
outlet e ,i
82,5
3
2 2
3 000 m /h
DUPLEX
unit
67,6
S-4500
inlet e ,i
69,3
1 1
400 V
M.012
outlet e ,i
87,3
3
2 2
4 350 m /h unit
73,3
inlet e ,i
63,1
1 1
400 V
M.010
outlet e ,i
85,3
3
2 2
3 750 m /h
DUPLEX
unit
68,2
S-5600
inlet e ,i
67,9
1 1
400 V
M.017
outlet e ,i
87,7
3
2 2
5 200 m /h unit
72,5
Type
Fan
Oper. point
Sound pressure level L [dB(A)]
D1
230 V unit
51,2
3
M.005
DUPLEX
1000 m /h
S-1500
230 V unit
52,4
3
M.007 1300 m /h
DUPLEX
230 V unit
50,8
3
M.014
S-2200
1800 m /h
400 V unit
56,9
3
M.010
DUPLEX
2650 m /h
S-3100
230 V unit
50,4
3
M.014 2100 m /h
400 V unit
56,6
3
M.011
DUPLEX
3000 m /h
S-4500
400 V unit
62,3
3
M.012 4350 m /h
400 V unit
57,2
3
M.010
DUPLEX
3750 m /h
S-5600
400 V unit
61,5
3
M.017 5200 m /h
The sound pressure level is measured at 1 m distance from a unit.
wall
wall
floor
floor
floor
Door-side manipulation space
Accessory-side manipulation space